Signals
Description
Z12Ang, Z23Ang, Z31Ang,
ZL1Ang, ZL2Ang, ZL3Ang
Phase-to-phase and phase-to-neutral impedance angles.
Rseq, Xseq, Zseq
RseqAng, XseqAng, ZseqAng
Positive sequence resistance, reactance and impedance values and angles.
GL1, GL2, GL3, G0
BL1, BL2, BL3, B0
YL1, YL2, YL3, Y0
Conductances, susceptances and admittances.
YL1angle, YL2angle, YL3angle,
Y0angle
Admittance angles.
Others
System f.
Used tracking frequency at the moment.
Ref f1
Reference frequency 1.
Ref f2
Reference frequency 2.
M thermal T
Motor thermal temperature.
F thermal T
Feeder thermal temperature.
T thermal T
Transformer thermal temperature.
RTD meas 1…16
RTD measurement channels 1…16.
Ext RTD meas 1…8
External RTD measurement channels 1…8 (ADAM module).
Settings
Table. 6.3 - 263. Settings.
Name
Range
Step Default
Description
Measurement value
recorder mode
0: Disabled
1: Activated
-
0:
Disabled
Activates and disables the real-time signals to
communication.
Scale current
values to primary
0: No
1: Yes
-
0: No
Selects whether or not values are scaled to
primary.
Slot X magnitude
selection
0: Currents
1: Voltages
2: Powers
3: Impedance (ZRX) and
admittance (YGB)
4: Others
-
0:
Currents
Selects the measured magnitude catecory of the
chosen slot.
Slot X magnitude
Described in table above
("Available measured values")
-
-
Selects the magnituge in the previously selected
category.
Magnitude X
-10 000 000.000…10 000
000.000
0.001 -
Displays the measured value of the selected
magnitude of the selected slot.
The unit depends on the selected magnitude
(either amperes, volts, or per-unit values).
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
369