Event number
Event channel
Event block name
Event code
Description
1421
22
NOC3
13
Phase A Trip OFF
1422
22
NOC3
14
Phase B Trip ON
1423
22
NOC3
15
Phase B Trip OFF
1424
22
NOC3
16
Phase C Trip ON
1425
22
NOC3
17
Phase C Trip OFF
1472
23
NOC4
0
Start ON
1473
23
NOC4
1
Start OFF
1474
23
NOC4
2
Trip ON
1475
23
NOC4
3
Trip OFF
1476
23
NOC4
4
Block ON
1477
23
NOC4
5
Block OFF
1478
23
NOC4
6
Phase A Start ON
1479
23
NOC4
7
Phase A Start OFF
1480
23
NOC4
8
Phase B Start ON
1481
23
NOC4
9
Phase B Start OFF
1482
23
NOC4
10
Phase C Start ON
1483
23
NOC4
11
Phase C Start OFF
1484
23
NOC4
12
Phase A Trip ON
1485
23
NOC4
13
Phase A Trip OFF
1486
23
NOC4
14
Phase B Trip ON
1487
23
NOC4
15
Phase B Trip OFF
1488
23
NOC4
16
Phase C Trip ON
1489
23
NOC4
17
Phase C Trip OFF
The function registers its operation into the last twelve (12) time-stamped registers; this information is
available for all provided instances separately. The register of the function records the ON event
process data for START, TRIP or BLOCKED. The table below presents the structure of the function's
register content.
Table. 5.3.2 - 54. Register content.
Date and
time
Event
code
Fault type
Pre-trigger
current
Fault
current
Pre-fault
current
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
1280-1489
Descr.
L1-E…L1-L2-L3
Start/Trip
-20ms
current
Start/
Trip current
Start
-200ms
current
0
ms...1800s
Setting group
1...8 active
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
104
© Arcteq Relays Ltd
IM00013