Pick-up
Pick-up current settings:
- I
SET
high limit
- I
SET
low limit
- I
SUM
difference
- I
SET
ratio
- I2/I1 ratio
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.01…100.00 %, setting step 0.01 %
0.01…100.00 %, setting step 0.01 %
Inaccuracy:
- Starting IL1, IL2, IL3
- Starting I2/I1
- Starting I01 (1 A)
- Starting I02 (0.2 A)
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
±1.0 %I2
SET
/ I1
SET
or ±100 mA (0.10…4.0 × I
N
)
±0.5 %I0
SET
or ±3 mA (0.005…10.0 × I
SET
)
±1.5 %I0
SET
or ±1.0 mA (0.005…25.0 × I
SET
)
Time delay for alarm
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy_
- Definite time (I
M
/I
SET
ratio > 1.05)
±2.0 % or ±80 ms
Instant operation time (alarm):
- I
M
/I
SET
ratio > 1.05
<80 ms (<50 ms in differential protection relays)
Reset
Reset ratio
97/103 % of the pick-up current setting
Instant reset time and start-up reset
<80 ms (<50 ms in differential protection relays)
9.2.3.2 Voltage transformer supervision (60)
Table. 9.2.3.2 - 307. Technical data for the voltage transformer supervision function.
Measurement inputs
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
Voltage input magnitudes
RMS line-to-line or line-to-neutral voltages
Pick-up
Pick-up settings:
- Voltage (low pick-up)
- Voltage (high pick-up)
- Angle shift limit
0.05…0.50 × U
N
, setting step 0.01 × U
N
0.50…1.10 × U
N
, setting step 0.01 × U
N
2.00…90.00 deg, setting step 0.10 deg
Inaccuracy:
- Voltage
- U angle (U> 1 V)
±1.5 %U
SET
±1.5°
External line/bus side pick-up (optional)
0
→
1
Time delay for alarm
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (U
M
/U
SET
ratio > 1.05/0.95)
±1.0 % or ±35 ms
Instant operation time (alarm):
- U
M
/U
SET
ratio > 1.05/0.95
<80 ms
VTS MCB trip bus/line (external input)
<50 ms
Reset
Reset ratio
97/103 % of the pick-up voltage setting
Reset time setting
Inaccuracy: Reset time
0.010…10.000 s, step 0.005 s
±2.0 % or ±80 ms
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
413
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......