Figure. 5.4.5 - 199. Example of timers and pick-up parameters (activated pick-up and instant release due to too long starting).
In the example above, the cold load pick-up function activates after the measured current has stayed
below the
I
low
setting for a
T
set
amount of time. When the current exceeds the
I
high
setting, a timer
starts counting towards the
T
max
time. The measured current stays above the
I
high
setting until the
T
max
is reached, which causes the release of the cold load pick-up signal.