Auto-recloser sequence from Trip with two shots (both fail).
In this auto-recloser scheme, the TRIP signal from the directional eath fault protection function (I0dir>
TRIP) was set up as the operation starter for Request 2 (REQ2). REQ2 has two shots (Shots 1 and 2)
enabled with the setting detailed in the image below; the first one is a high-speed shot (0.2 s) that is
then followed by a time-delayed shot (60 s).
Figure. 5.4.4 - 180. Settings for I0dir> with two shots.
When the TRIP signal is used to initiate the auto-recloser sequence, no additional starting or
discrimination times are needed as the protection stage's own operation takes care of the breaker
opening timings directly. Therefore, the auto-recloser function only monitors the status of the directional
earth fault stage's tripping before initiating requests and shots.
Figure. 5.4.4 - 181. Signal status graph of the permanent earth fault auto-recloser cycle.
1. An earth fault is found in the protected line causing the I0Dir> protection to start
calculating the operating time for a trip.
2. The I0Dir> trips and gives the "Open" command to the breaker's open coil. The auto-
recloser function is initiated and the AR Running
AR Running, AR2 R
AR2 Request
equested
ed and SSho
hot 1 Running
t 1 Running signals
are activated.
3. The circuit breaker is opened and the I0Dir> TRIP signal is released and simultaneously the
REQ2 trip signal for the auto-recloser is released. The recloser starts calculating the SSho
hot1
t1
Dead T
Dead Time
ime to close the breaker.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
264
© Arcteq Relays Ltd
IM00013