Name
Range
Step
Default
Description
Continue
time
calculation
during
release
time
1: No
2: Yes
-
1: No
Time calculation characteristics selection. If activated, the operating time
counter is continuing until a set release time has passed even if the pick-
up element is reset.
The user can reset characteristics through the application. The default setting is a 60 ms delay; the
time calculation is held during the release time.
In the release delay option the operating time counter calculates the operating time during the release.
When using this option the function does not trip if the input signal is not re-activated while the release
time count is on-going.
Events and registers
The overvoltage function (abbreviated "OV" in event block names) generates events and registers from
the status changes in START, TRIP, and BLOCKED. The user can select which event messages are
stored in the main event buffer: ON, OFF, or both. The function offers four (4) independent stages;
the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.10 - 106. Event codes.
Event number
Event channel
Event block name
Event code
Description
5440
85
OV1
0
Start ON
5441
85
OV1
1
Start OFF
5442
85
OV1
2
Trip ON
5443
85
OV1
3
Trip OFF
5444
85
OV1
4
Block ON
5445
85
OV1
5
Block OFF
5504
86
OV2
0
Start ON
5505
86
OV2
1
Start OFF
5506
86
OV2
2
Trip ON
5507
86
OV2
3
Trip OFF
5508
86
OV2
4
Block ON
5509
86
OV2
5
Block OFF
5568
87
OV3
0
Start ON
5569
87
OV3
1
Start OFF
5570
87
OV3
2
Trip ON
5571
87
OV3
3
Trip OFF
5572
87
OV3
4
Block ON
5573
87
OV3
5
Block OFF
5632
88
OV4
0
Start ON
5633
88
OV4
1
Start OFF
5634
88
OV4
2
Trip ON
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
172
© Arcteq Relays Ltd
IM00013
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......