The device has a maximum limit of 100 for the number of recordings. Even when the recordings are
very small, their number cannot exceed 100. The number of analog and digital channels together with
the sample rate and the time setting affect the recording size. See calculation examples below in the
section titled "Estimating the maximum length of total recording time".
Table. 5.5.6 - 240. Recorder control settings.
Name
Range
Step
Default
Description
Recorder
enabled
0: Enabled
1: Disabled
-
0:
Enabled Enables and disables the disturbance recorder function.
Recorder
status
0: Recorder ready
1: Recording
triggered
2: Recording and
storing
3: Storing
recording
4: Recorder full
5: Wrong config
-
-
Indicates the status of recorder.
Clear
0…2
32
-1
1
-
Clears selected recording. If "1" is inserted, first recording will be
cleared from memory. If "10" is inserted, tenth (10th) recording will be
cleared from memory.
Manual
trigger
0: -
1: Trig
-
0: -
Triggers disturbance recording manually. This parameter will return
back to "-" automatically.
Clear all
records
0: -
1: Clear
-
0: -
Clears all disturbance recordings.
Clear
newest
record
0: -
1: Clear
-
0: -
Clears the newest stored disturbance recording.
Clear
oldest
record
0: -
1: Clear
-
0: -
Clears the oldest stored disturbance recording.
Max.
number of
recordings
0…100
1
-
Displays the maximum number of recordings that can be stored in the
device's memory with settings currently in use. The maximum number
of recordings can go up to 100.
Max.
length of a
recording
0.000...1800.000s 0.001s -
Displays the maximum length of a single recording.
Max.
location of
the pre-
trigger
0.000...1800.000s 0.001s -
Displays the highest pre-triggering time that can be set with the
settings currently in use.
Recordings
in memory
0…100
1
-
Displays how many recordings are stored in the memory.
Table. 5.5.6 - 241. Recorder trigger setting.
Name
Description
Recorder
trigger
Selects the trigger input(s). Clicking the "Edit" button brings up a pop-up window, and checking the boxes
enable the selected triggers.
Table. 5.5.6 - 242. Recorder settings.
Name
Range
Step Default
Description
Recording length 0.100...1800.000s 0.01s 1s
Sets the length of a recording.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
345
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......