Trip, Retrip and CBFP in the device configuration
Figure. 5.3.8 - 102. Wiring diagram when Trip, Retrip and CBFP are configured to the device.
The retrip functionality can be used in applications whose circuit breaker has a retrip or a redundant
trip coil available. The TRIP signal is normally wired to the breaker's trip coil from the device's trip
output. The retrip is wired from its own device output contact in parallel with the circuit breaker's
redundant trip coil. The CBFP signal is normally wired from its device output contact to the incomer
breaker. Below are a few operational cases regarding the various applications.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
147
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......