Table. 5.2.1 - 22. Sequence phase angle measurements.
Name
Unit
Range
Step
Description
Positive sequence current angle
("Positive sequence curr.angle")
deg
0.00…360.00
0.01
The calculated positive sequence current angle.
Negative sequence current angle
("Negative sequence curr.angle")
deg
0.00…360.00
0.01
The calculated negative sequence current angle.
Zero sequence current angle
("Zero sequence curr.angle")
deg
0.00…360.00
0.01
The calculated zero sequence current angle.
Table. 5.2.1 - 23. Harmonic current measurements.
Name
Range
Step Default
Description
Harmonics
calculation values
("Harm Abs.or
Perc.")
-
0: Percent
1: Absolute
-
0:
Percent
Defines whether the harmonics are calculated as percentage
or absolute values.
Harmonics display -
0: Per unit
1: Primary A
2: Secondary A
-
0: Per
unit
Defines how the harmonics are displayed: in p.u values, as
primary current values, or as secondary current values.
Maximum
harmonics value
("Ixx maximum
harmonic")
A 0.00...100000.00 0.01
-
Displays the maximum harmonics value of the selected
current input ILx or I0x.
Fundamental
frequency
("Ixx
fundamental")
A 0.00...100000.00 0.01
-
Displays the current value of the fundamental frequency
(RMS) from the selected current input ILx or I0x.
Ixx harmonics
(2
nd
...31
st
harmonic)
A 0.00…100000.00 0.01
-
Displays the selected harmonic from the current input ILx or
I0x.
5.2.2 Voltage measurement and scaling
The voltage measurement module (VT module, or VTM) is used for measuring the voltages from
voltage transformers. The measured values are processed into the measurement database and they
are used by measurement and protection functions (the protection function availability depends of the
relay type). It is essential to understand the concept of voltage measurements to be able to get correct
measurements.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
68
© Arcteq Relays Ltd
IM00013