Figure. 5.4.5 - 198. Example of timers and pick-up parameters (activated pick-up and instant release due to overcurrent).
In the example above, the cold load pick-up function activates after the measured current dips below
the
I
low
setting and has been there for
T
set
amount of time. When the
I
m
exceeds the
I
high
setting, a
counter starts counting towards the
T
max
time. The measured current exceeds the
I
over
setting during
the start-up situation and causes the cold load pick-up signal to be released immediately.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
292
© Arcteq Relays Ltd
IM00013