Name
Range
Description/values
2: Timing status
- TF> Trip delay remaining: the time to reach 100% theta
- TF> Trip time to rel.: the time to reach theta while staying below the trip limit during
cooling
- TF> Alarm 1 time to rel.: the time to reach theta while staying below the Alarm 1 limit
during cooling
- TF> Alarm 2 time to rel.: the time to reach theta while staying below the Alarm 2 limit
during cooling
- TF> Inhibit time to rel.: the time to reach theta while staying below the Inhibit limit during
cooling
Table. 5.3.19 - 162. Counters.
Name
Description / values
Alarm1 inits
The number of times the function has activated the Alarm 1 output
Alarm2 inits
The number of times the function has activated the Alarm 2 output
Restart inhibits
The number of times the function has activated the Restart inhibit output
Trips
The number of times the function has tripped
Trips Blocked
The number of times the function trips has been blocked
Events and registers
The line thermal overload protection function (abbreviated "TOLF" in event block names) generates
events and registers from the status changes in TRIP and BLOCKED signals. The user can select
which event messages are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.19 - 163. Event codes.
Event number
Event channel
Event block name
Event code
Description
4288
67
TOLF1
0
Alarm1 ON
4289
67
TOLF1
1
Alarm1 OFF
4290
67
TOLF1
2
Alarm2 ON
4291
67
TOLF1
3
Alarm2 OFF
4292
67
TOLF1
4
Inhibit ON
4293
67
TOLF1
5
Inhibit OFF
4294
67
TOLF1
6
Trip ON
4295
67
TOLF1
7
Trip OFF
4296
67
TOLF1
8
Block ON
4297
67
TOLF1
9
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for TRIP or BLOCKED. The table below presents the
structure of the function's register content.
Table. 5.3.19 - 164. Register content.
Name
Description
Date and time
dd.mm.yyyy hh:mm:ss.mss
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
236
© Arcteq Relays Ltd
IM00013
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......