Figure. 4.4 - 14. I/O.
The "I/O" section is divided into two subsections: "Direct output control" and "Blocking input control".
In "Direct output control" you can connect the stage's signals to physical outputs, either to an output
relay or an LED (START or TRIP LEDs or one of the 16 user configurable LEDs). If the stage is blocked
internally (DI or another signal), you can configure an output to indicate the stage that is blocked. A
connection to an output can be either latched ("|x|") or non-latched ("x").
"Blocking input control" allows you to block stages. The blocking can be done by using any of the
following:
• digital inputs
• logical inputs or outputs
• the START, TRIP or BLOCKED information of another protection stage
• object status information.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
23
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......