Section 4
1MAC309294-MB F
Protection functions
162
RER620
Technical Manual
System neutral grounding is meant to protect personnel and equipment and to reduce
interference for example in telecommunication systems. The neutral grounding creates
challenges for protection systems, especially for ground-fault protection.
In isolated networks, there is no intentional connection between the system neutral point
and ground. The only connection is through the line-to-ground capacitances (C
0
) of phases
and leakage resistances (R
0
). This means that the zero sequence current is mainly
capacitive and has –90 degrees phase shift compared to the zero sequence voltage (-V
0
).
The characteristic angle is -90 degrees.
In resonance-grounded networks, the capacitive fault current and the inductive resonance
coil current compensate each other. The protection cannot be based on the reactive current
measurement, since the current of the compensation coil would disturb the operation of the
relays. In this case, the selectivity is based on the measurement of the active current
component. This means that the zero sequence current is mainly resistive and has zero
phase shift compared to the zero sequence voltage (-V
0
) and the characteristic angle is 0
degrees. Often the magnitude of this component is small, and must be increased by means
of a parallel resistor in the compensation equipment.
In networks where the neutral point is grounded through low resistance, the characteristic
angle is also 0 degrees (for phase angle). Alternatively, I
0
cos(φ) operation can be used.
In solidly grounded networks, the
Characteristic angle
is typically set to +60 degrees for
the phase angle. Alternatively, I
0
sin(φ) operation can be used with a reversal polarizing
quantity. The polarizing quantity can be rotated 180 degrees by setting the
Pol reversal
parameter to “True” or by switching the polarity of the zero sequence voltage
measurement wires. Although the I
0
sin(φ) operation can be used in solidly grounded
networks, the phase angle is recommended. In some applications, negative sequence
polarization is preferred over zero sequence polarization. The relay also offers negative
sequence polarization option where users can set the angle between V
2
and I
2
based on
their application and practice.
Connection of measuring transformers in directional ground fault
applications
The zero sequence current I
0
can be measured with a core balance current transformer or
the residual connection of the phase current signals. If the neutral of the network is either
isolated or grounded with high impedance, a core balance current transformer is
recommended to be used in ground-fault protection. To ensure sufficient accuracy of zero
sequence current measurements and consequently the selectivity of the scheme, the core
balance current transformers should have a transformation ratio of at least 70:1. Lower
transformation ratios such as 50:1 or 50:5 are not recommended.
Attention should be paid to make sure the measuring transformers are connected correctly
so that 67/51N and 67/50N is able to detect the fault current direction without failure. As
directional ground fault uses zero sequence current and zero sequence voltage (-V
0
), the
polarities of the measuring transformers must match each other and also the fault current
direction. Also the grounding of the cable sheath must be taken into consideration when
using core balance current transformers. The following figure describes how measuring
transformers can be connected to the relay.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......