Section 7
1MAC309294-MB F
Measurement functions
388
RER620
Technical Manual
Figure 208:
Integral deadband supervision
The deadband value used in the integral calculation is configured with the
X deadband
setting. The value represents the percentage of the difference between the maximum and
minimum limit in the units of 0.001 percent * seconds.
The reporting delay of the integral algorithms in seconds is calculated with the formula:
(Equation 43)
Example for IA, IB, IC:
A deadband = 2500 (2.5% of the total measuring range of 40)
I_INST_A
=
I_DB_A
= 0.30
If
I_INST_A
changes to 0.40, the reporting delay is:
t s
deadband
Y
( )
(max min)
/
%
=
−
×
×
1000
100
Δ
t s
s
( )
(
)
/
.
.
%
=
− ×
−
×
=
40 0
2500 1000
0 40 0 30 100
10
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......