1MAC309294-MB F
Section 5
Control functions
RER620
285
Technical Manual
5.2.3.2
Protection signal definition
The
Control line
setting defines which of the initiation signals are protection pickup and
trip signals and which are not. With this setting, the user can distinguish the blocking
signals from the protection signals. The
Control line
setting is a bit mask, that is, the lowest
bit controls the
INIT_1
line and the highest bit the
INIT_6
line. Some example
combinations of the
Control line
setting are as follows:
Table 293: Control line setting definition
prot =
protection signal
other =
non-protection signal
When the corresponding bit or bits in both the
Control line
setting and the
INIT_X
line
are TRUE:
• The
CLOSE_CB
output is blocked until the protection is reset
• If the
INIT_X
line defined as the protection signal is activated during the
discrimination time, the AR function goes to lockout
• If the
INIT_X
line defined as the protection signal stays active longer than the time
set by the
Max trip time
setting, the AR function goes to lockout (long trip)
• The
UNSUC_RECL
output is activated after a pre-defined two minutes (alarming
ground-fault).
It is emphasized that the three phases of the same protection function should be fed to the
same INIT input to the autorecloser.
5.2.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “On” and “Off”.
The reclosing operation can be enabled and disabled with the
Reclosing operation
setting.
This setting does not disable the function, only the reclosing functionality. The setting has
three parameter values: “On”, “External Ctl” and “Off”. The setting value “On” enables
the reclosing operation and “Off” disables it. When the setting value “External Ctl” is
selected, the reclosing operation is controlled with the
RECL_ON
input.
Control line
setting
INIT_1
INIT_2
INIT_3
INIT_4
INIT_5
INIT_6
0
other
other
other
other
other
other
1
prot
other
other
other
other
other
2
other
prot
other
other
other
other
3
prot
prot
other
other
other
other
4
other
other
prot
other
other
other
5
prot
other
prot
other
other
other
...63
prot
prot
prot
prot
prot
prot
Setting the
Operation
setting to “Off” will prevent tripping by any
protection function!
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......