1MAC309294-MB F
Section 4
Protection functions
RER620
99
Technical Manual
Table 119: 50P-1/2 Monitored data
Table 120: 50P-3 Monitored data
4.1.1.11
Technical data
Table 121: 51P/50P Technical data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50P-1/2
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50P-3
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Operation
accuracy
Depending on the frequency of the current measured: f
n
±2Hz
51P
±1.5% of the set value or ±0.002 x I
n
50P-1/2
and
50P-3
±1.5% of set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Pickup time
12
1.
Measurement mode
= default (depends on stage), current before fault = 0.0 x I
n
, f
n
= 60 Hz, fault current in
one phase with nominal frequency injected from random phase angle, results based on statistical distribution
of 1000 measurements
2. Includes the delay of the signal output contact
Minimum
Typical
Maximum
50P-3:
I
Fault
= 2 x set
Pickup value
I
Fault
= 10 x set
Pickup
value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
51P and 50P-1/2:
I
Fault
= 2 x set
Pickup
value
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3
3. Maximum
Pickup value
= 2.5 x I
n
,
Pickup value
multiples in range of 1.5 to 20
Suppression of harmonics
RMS: No suppression
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......