1MAC309294-MB F
Section 4
Protection functions
RER620
269
Technical Manual
Table 279: Recommended Characteristic angle setting for different network
The
Characteristic angle
setting is adjusted to the operation according to the method of
neutral point earthing so that in an isolated network the
Characteristic angle
= -90° and in
a compensated network = 0°. In addition, the
Characteristic angle
can be changed via the
control signal RCA_CTL, in which case the alternatives are -90° and 0°. The operation of
the RCA_CTL depends on the
Characteristic angle
setting.
The Peterson coil or the earthing resistor may be temporarily out of operation. To keep the
protection scheme selective, it is necessary to update the
Characteristic angle
accordingly.
This is done with an auxiliary input in the relay which receives a signal from an auxiliary
switch of the disconnector of the Peterson coil in compensated networks or of the earthing
resistor in earthed network as a result the
Characteristic angle
is set automatically to suit
the earthing method. The table below shows the
Characteristic angle
control for
RCA_CTL condition.
Table 280: Characteristic angle control for RCA_CTL condition
Low level blocking
For reliable operation, signals levels should be greater than minimum level. If they are not
greater than minimum level, Timer is blocked.
In “Neg. seq. volt.” polarization selection using
Pol signal Sel
, if the amplitude of the
negative sequence current is greater than
Min operate current
value and negative sequence
voltage amplitude is greater than
Min operate voltage
value then enable signal is sent to
the Timer.
In “Measured VG” or “Calculated VN” polarization selection using
Pol signal Sel
, if the
amplitude of the residual current is greater than the
Min operate current
value and residual
voltage amplitude is greater than the
Min operate voltage
value then enable signal is sent
to the Timer.
Timer
Once activated the internal operate timer is started. The timer characteristic is according
to Definite Time (DT). When the Timer has reached the value of
Release delay time
, the
RELEASE output is activated. If a drop-off situation happens, that is, if operating current
moves out of the operating sector or signal amplitudes become below the minimum levels,
before the
Release delay time
is exceeded, the timer reset state is activated. If drop off
continues for more than
Reset delay time
the Timer is deactivated.
Type of network
Characteristic angle recommended
Compensated network
0 ˚
Solidly earthed network
+60 ˚
Isolated network
-90 ˚
Characteristic angle
Setting
RCA_CTL=FALSE
RCA_CTL=TRUE
-90°
Characteristic angle
= -90°
Characteristic angle
= 0°.
0°.
Characteristic angle
= 0°.
Characteristic angle
= -90°
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......