1MAC309294-MB F
Section 8
Recording functions
RER620
415
Technical Manual
user can monitor the time remaining to the next triggering with the
Time to trigger
monitored data which counts downwards.
8.1.2
Length of recordings
The user can define the length of a recording with the
Record length
parameter. The length
is given as the number of fundamental cycles.
According to the memory available and the number of analog channels used, the digital
fault recorder automatically calculates the remaining amount of recordings that fit into the
available recording memory. The user can see this information with the
Rem. amount
of rec
monitored data. The fixed memory size allocated for the recorder can fit in two
recordings that are ten seconds long. The recordings contain data from all analog and
binary channels of the digital fault recorder, at the sample rate of 32 samples per
fundamental cycle.
The user can view the number of recordings currently in memory with the
Number of
recordings
monitored data. The currently used memory space can be viewed with the
Rec. memory used
monitored data. It is shown as a percentage value.
8.1.2.1
Sampling frequencies
The sampling frequency of the digital fault recorder analog channels depends on the set
rated frequency. One fundamental cycle always contains the amount of samples set with
the
Storage rate
parameter. Since the states of the binary channels are sampled once per
task execution of the digital fault recorder, the sampling frequency of binary channels is
400 Hz at the rated frequency of 50 Hz and 480 Hz at the rated frequency of 60 Hz.
Table 377: Sampling frequencies of the digital fault recorder analog channels
8.1.2.2
Uploading of recordings
The relay stores COMTRADE files to the
C:\COMTRADE\
folder. The files can be
uploaded with the PCM tool or any appropriate computer software that can access the
C:\COMTRADE\
folder.
The maximum number of recordings is 100.
Storage rate
(samples per
fundamental
cycle)
Recording
length
Sampling
frequency of
analog
channels, when
the rated
frequency is 50
Hz
Sampling
frequency of
binary
channels, when
the rated
frequency is 50
Hz
Sampling
frequency of
analog
channels, when
the rated
frequency is 60
Hz
Sampling
frequency of
binary
channels, when
the rated
frequency is 60
Hz
32
1* Record
length
1600 Hz
400 Hz
1920 Hz
480 Hz
16
2* Record
length
800 Hz
400 Hz
960 Hz
480 Hz
8
4 * Record
length
400 Hz
400 Hz
480 Hz
480 Hz
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......