1MAC309294-MB F
Section 9
Other functions
RER620
423
Technical Manual
Section 9
Other functions
9.1
Uninterruptible Power Supply UPS
9.1.1
Function block
Figure 219:
UPS function block
9.1.2
Functionality
The RER620 UPS (Uninterruptible Power Supply) is a subsystem for the RER620 recloser
controller. It is implemented in a separate case (see Figure 220) and is powered by the
control power which may be AC or DC. The UPS can operate over a wide range of control
voltages.
The main UPS function is to enable operation of the RER620 after the loss of control
power for a period of time that depends on the amp hour rating of the battery. A 12 amp
hour battery will power the total system for about 38 hours with a standard load. The
RER620 UPS incorporates a battery management system that includes both battery
charging and battery test functions.
The RER620 UPS case includes an auxiliary power output that may be used to power a
modem, radio, etc.
There is also a voltage boost function integrated into the RER620 UPS system that
provides up to 250Vdc. This power source, in combination with an external capacitor, is
used to operate a variety of magnetic actuators.
The UPS incorporates a high current dry contact output that is temperature controlled. This
output can be used to switch on and off the low-voltage-cabinet heater.
The RER620 UPS is microprocessor controlled and is capable of external communications
through its communications port. The main purpose for this communication is to receive
instructions from the RER620 Control and to transmit status, and battery test results to the
RER620 Control.
ZBAT1
START_TST
AC_LOSS
TST_RESULT
CVD_CLP_A
CVD_CLP_B
CVD_CLP_C
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......