1MAC309294-MB F
Section 4
Protection functions
RER620
127
Technical Manual
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the
percentual ratio of the pickup situation and the set trip time. The value is available through
the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting “
Configuration/System/
Blocking
mode”
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
signal activation is preselected with the global setting
Blocking
mode
.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
trip timer is frozen to the prevailing value. In the “Block all” mode, the whole function is
blocked and the timers are reset. the “Block TRIP output” mode, the function operates
normally but the
TRIP
output is not activated.
4.1.3.5
Measurement modes
The function operates on three alternative measurement modes: “RMS”, “DFT” and
“Peak-to-Peak”. The measurement mode is selected with the
Measurement mode
setting.
Table 143: Measurement modes supported by 51N/50N or 51G/50G stages
4.1.3.6
Timer characteristics
51N/50N or 51G/50G supports both DT and IDMT characteristics. The user can select the
timer characteristics with the
Operating curve type
and
Type of reset curve
settings. When
the DT characteristic is selected, it is only affected by the
Trip delay time
and
Reset delay
time
settings.
The relay provides 16 IDMT characteristics curves, of which seven comply with the IEEE
C37.112 and six with the IEC 60255-3 standard. Two curves follow the special
characteristics of ABB praxis and are referred to as RI and RD. In addition to this, a user
programmable curve can be used if none of the standard curves are applicable. The user
The
Minimum trip time
setting should be used with great care because the
operation time is according to the IDMT curve, but always at least the value
of the
Minimum operate time
setting. For more information, see the
General function block features section in this manual
Measurement
mode
Supported measurement modes
51N/G
50N/G-1/2
50N/G-3
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
x
For a detailed description of the measurement modes, see the General
function block features section in this manual.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......