Section 3
1MAC309294-MB F
Basic functions
52
RER620
Technical Manual
Table 33:
Settings
Not all parameters belong to a setting group. For example protection function
enable/disable settings are not part of a setting group.
3.6
Recorded data
The relay has the capacity to store the records of 32 latest fault events. The records enable
the user to analyze the 32 most recent power system events. Each fault record (FLTMSTA)
is marked with an up-counting fault number. Slot fault record 1 always contains the newest
record, and fault record 32 the oldest. The time stamp is taken from the beginning of the
fault.
The fault recording period begins from the pickup event of any protection function and
ends if any protection function trips or the pickup(s) is restored before the trip event. The
type of fault that triggers the fault recording is selected with the setting parameter
Trig
mode
. When “From all faults” is selected, all types of detected faults trigger a new fault
recording. When “From trip” is selected, only faults that cause an trip event trigger a new
fault recording.Finally when From only pickup is selected, only faults that cause a
protection function restoring before the actual trip signal are recorded.
Fault recorder (FLR) collects some minimum and maximum current and voltage values
during the recording period. DFT, RMS or Peak-to-Peak can be set as the generic
measuring mode with setting parameter
Measurement mode
. The recording of the
maximum and minimum phase currents, maximum ground current and maximum ground
voltage is affected by the selected measuring mode and the maximum current and voltage
values are still collected 50 ms after the recording period is closed. In addition, the
maximum demand current is separately recorded with time stamp.
Fault recorder also provides
Operation
parameter that can be used for setting the recorder
into Enable/Disable and BLOCK input that can be used for blocking the recording
triggering by using logic, for example during the auto-reclosing sequence. The recorded
data can be separately cleared with parameters in the Clear menu.
The data recorded depend on the product and the standard configuration.
Parameter
Setting
Value
Default
Description
Access rights
Setting group
Active group
1...4
1
Selected
active group
RWRW
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......