Figure 147:
Initiation input signals
In total, the AR function contains six separate initiation lines used for the initiation or
blocking of the auto-reclose shots.
Figure 148:
Signal scheme of auto-reclose operation initiated with protection operate
signal
The auto-reclose shot is initiated with a trip signal of the protection function. The
auto-reclose starts when the protection operate delay time elapses. Normally, all trip and
start signals are used to initiate an auto-reclose shot and trip the circuit breaker. If any of
the input signals INIT_X are used for blocking, the corresponding bit in the
Tripping line
setting must be FALSE. This is to ensure that the circuit breaker does not trip from that
signal, that is, the signal does not activate the OPEN_CB output. The default value for the
INPUT to CBB’s
Initiation signal (bit 1)
INIT_1
Initiation signal
Tripping line
AND
(bitwise)
OPEN_CB
> 0
Initiation signal (bit 2)
INIT_2
Initiation signal (bit 3)
INIT_3
Initiation signal (bit 4)
INIT_4
Initiation signal (bit 5)
INIT_5
Initiation signal (bit 6)
INIT_6
Instant of
fault
INIT_1
Operate signal
from protection
Start signal from
protection
OPEN_CB
CLOSE_CB
Operate delay time
Reclose time
Reclaim time
Circuit breaker (CB) status
CLOSED
OPEN
CLOSED
Protection
pick-up
Protection trip /
operate
CB reclose
command
Succesful
reclosing
ACTIVE
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......