1MAC309294-MB F
Section 13
Technical data
RER620
567
Technical Manual
Table 456: Degree of protection of flush-mounted relay
Table 457: Environmental conditions
Table 458: Environmental tests
Description
Value
Front side
IP 54
Back side
IP 20
Description
Value
Continuous operating temperature range
-25ºC to +55ºC
Short-term operating temperature range
-40ºC to +85ºC (<12h)
1 , 2
1. Degradation in MTBF and LHMI performance outside the temperature range of -25ºC to +55ºC
2. For relays with an LC communication interface, the maximum operating temperature is +70ºC
Relative humidity
<93%, non-condensing
Atmospheric pressure
12.47 to 15.37 psi (86 to 106 kPa)
Altitude
Up to 6561.66 feet (2000 m)
Transport and storage temperature range
-40ºC to +85ºC
Description
Requirement
Reference
Dry heat test
+85ºC 12h
1 , 2
1. For relays with an LC communication interface, the maximum operating temperature is +70
o
C.
2. LCD may be unreadable, but relay is operational.
IEEE C37.90-2005
Dry cold test
-40ºC 12h
2, 3
3. For PS_L (24-60 Vdc), the minimum start up voltage is 48Vdc at -40ºC.
IEEE C37.90-2005
Damp heat test
+25ºC Rh = 95%, 96h
IEEE C37.90-2005
Storage test
+85ºC 96h -40ºC 96h
IEEE C37.90-2005
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......