Section 4
1MAC309294-MB F
Protection functions
258
RER620
Technical Manual
M = Distance to point of fault from relay location
4.5.4.6
Signals
Table 269: FLO input signals
4.5.4.7
Settings
Table 270: FLO group settings
4.5.4.8
Monitored data
Table 271: FLO monitored data
Name
Type
Default
Description
V_A
SIGNAL
0
Phase A Voltage
V_B
SIGNAL
0
Phase B Voltage
V_C
SIGNAL
0
Phase C Voltage
I_A
SIGNAL
0
Phase A Current
I_B
SIGNAL
0
Phase B Current
I_C
SIGNAL
0
Phase C Current
Parameter
Values (Range) Unit
Step
Default
Description
Operation
ON/OFF
ON
Operation
Line Length
0.00…300.00
Miles/Kms
100.00
Length of the transmission or distribution line in miles
R1
0.000...20.000
Ohm/(Mile or Km)
1.000
Positive sequence resistance of line in primary Ohm/(Mile or Km)
X1
0.000...30.000
Ohm/(Mile or Km)
2.000
Positive sequence reactance of line in primary Ohm/(Mile or Km)
R0
0.000...20.000
Ohm/(Mile or Km)
0.010
Zero sequence resistance of line in primary Ohm/(Mile or Km)
X0
0.000...30.000
Ohm/(Mile or Km)
1.000
Zero sequence reactance of line in primary Ohm/(Mile or Km)
Phase Level
0.00...40.00
%In
0.10
Threshold magnitude of phase current in the per-unit of primary
rated current
Name
Type
Description
FLT_DIST
FLOAT32
Estimated distance to fault in Miles or Kms depending on Line parameter units
FLT_R
FLOAT32
Estimated fault resistance in ohms
XF_LOOP
FLOAT32
Estimated reactance in the fault loop in ohms
FLT_LOOP
-1=ABG Fault
-2=BCG Fault
-3=CAG Fault
-4=ABCG Fault
0=No Fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Fault loop
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......