1MAC309294-MB F
Section 5
Control functions
RER620
295
Technical Manual
• Both: the automatic initiation is allowed when synchronization fails or the circuit
breaker does not close.
Figure 151:
Example of an auto-initiation sequence with synchronization failure in the
first shot and circuit breaker closing failure in the second shot
In the first shot, the synchronization condition is not fulfilled (
SYNC
is FALSE). When the
auto wait timer elapses, the sequence continues to the second shot. During the second
reclosing, the synchronization condition is fulfilled and the close command is given to the
circuit breaker after the second reclose time has elapsed.
After the second shot, the circuit breaker fails to close when the wait close time has
elapsed. The third shot is started and a new close command is given after the third reclose
time has elapsed. The circuit breaker closes normally and the reclaim time starts. When the
reclaim time has elapsed, the sequence is concluded successful.
Shot initiation and shot sequencing Possibilities
The autoreclose function is initiated after the protection has detected a fault, issued a trip
and opened the breaker. One input is enough for initiating the function.
The function consists of six individual initiation lines
INIT_1, INIT_2... INIT 6
.
The user can use as many of the initiation lines as required. Using only one line makes
setting easier, whereas by using multiple lines, higher functionality can be achieved.
Basically, there are no differences between the initiation lines.
The
Auto init
parameter defines which
INIT_X
lines are activated in the
auto-initiation. The default value for this parameter is “0”, which means
that no auto-initiation is selected.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......