Section 4
1MAC309294-MB F
Protection functions
232
RER620
Technical Manual
Table 242: Setting for a five-step underfrequency operation
The rate of change of frequency function is not instantaneous since the function needs time
to supply a stable value. It is recommended to have a time delay long enough to take care
of the signal noise.
Small industrial systems can experience the rate of change of frequency as large as 5 Hz/s
due to a single event. Even large power systems can form small islands with a large
imbalance between the load and generation when severe faults or combinations of faults
are cleared. Up to 3 Hz/s has been experienced when a small island becomes isolated from
a large system. For normal severe disturbances in large power systems, the rate of change
of the frequency is much less, often just a fraction of 1.0 Hz/s.
Similarly, the setting for df/dt can be from 0.1 Hz/s to 1.2 Hz/s in steps of 0.1 Hz/s to 0.3
Hz/s for large distributed power networks, with the operating time varying from a few
seconds to a few fractions of a second. Here, the operating time should be kept in minimum
for the higher df/dt setting.
Table 243: Setting for a five-step df/dt< operation
Once the frequency has stabilized, the shed load can be restored. The restoring operation
should be done stepwise, taking care that it does not lead the system back to the emergency
condition.
Load-shedding steps
Start value Freq
setting
Operate Tm Freq
setting
1
0.984 x Fn (49.2 Hz)
45000 ms
2
0.978 x Fn (48.9 Hz)
30000 ms
3
0.968 x Fn (48.4 Hz)
15000 ms
4
0.958 x Fn (47.9 Hz)
5000ms
5
0.950 x Fn (47.5 Hz)
500 ms
Load-shedding steps
Start value df/dt
setting
Operate Tm df/dt
setting
1
-0.005 xFn /s (-0.25 Hz/s)
8000 ms
2
-0.010 x Fn /s (-0.50 Hz/s)
2000 ms
3
-0.015 x Fn /s (-0.75 Hz/s)
1000 ms
4
-0.020 x Fn /s (-1.00 Hz/s)
500 ms
5
-0.025 x Fn /s (-1.25 Hz/s)
250 ms
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......