![ABB RER620 Technical Manual Download Page 90](http://html.mh-extra.com/html/abb/rer620/rer620_technical-manual_3180090.webp)
Section 4
1MAC309294-MB F
Protection functions
84
RER620
Technical Manual
The single-phase non-directional overcurrent protection function is used as one-phase and
three-phase overcurrent and short circuit protection. The phase-tripping mode is selected
with the Configuration setting
Recloser type
.
The operation in either tripping mode can be described by using a module diagram (see
Figure 35). Some modules have different functionality depending on whether the function
is in one-phase or three-phase tripping mode. All the blocks in the diagram are explained
in the next sections.
Figure 35:
Functional module diagram. I_A, I_B and I_C represent phase currents.
Level detector
The measured phase currents are compared phase-wise with the set
Pickup value
.and, if
enabled, the
Pickup block value
. If the measured value exceeds the set
Pickup value
, and
is less than the
Pickup block value
, the level detector reports the pickup to the phase
selection logic. If the
ENA_MULT
input is active, the
Pickup value
setting is multiplied by
the
Pickup value Mult
setting.
Do not set the multiplier setting
Pickup value Mult
higher than necessary.
If the value is too high, the function may not trip at all during an inrush
followed by a fault, no matter how severe the fault is.
The relay does not accept the Pickup value or Pickup value Mult setting if
the product of these settings exceeds the Pickup value setting range.
TRIP_C
I_A
I_B
I_C
BLOCK
PICKUP_C
Blocking
logic
ENA_MULT
t
Timer
t
Phase
selection
logic
Level
detector
t
Timer
t
t
Timer
t
PICKUP_B
TRIP_B
TRIP_A
PICKUP_A
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......