![ABB RER620 Technical Manual Download Page 277](http://html.mh-extra.com/html/abb/rer620/rer620_technical-manual_3180277.webp)
1MAC309294-MB F
Section 4
Protection functions
RER620
271
Technical Manual
4.5.6.7
Settings
Table 284: 32N group settings
Table 285: 32N non-group setting
4.5.6.8
Monitored data
Table 286: 32N Monitored data
4.5.6.9
Technical data
Table 287: 32N Technical data
Name
Values (Range)
Step Unit
Default
Description
Directional mode
1=Non-directional
2=Forward
3=Reverse
1
-
2=Forward
Directional mode of operation
Max forward angle
0…180
1
Deg
88
Maximum phase angle in forward direction
Max reverse angle
0…180
1
Deg
88
Maximum phase angle in reverse direction
Min forward angle
0…180
1
Deg
88
Minimum phase angle in forward direction
Min reverse angle
0…180
1
Deg
88
Minimum phase angle in reverse direction
Characteristic angle
-179…180
1
Deg
60
Characteristic angle
Release delay time
0…1000
1
ms
10
Release delay time
Name
Values (Range)
Step
Unit Default
Description
Operation
0=Off
1=On
1=ON
Operation Off / On
Reset delay time
0…60000
1
ms
20
Reset delay time
Pol reversal
0=False
1=True
1=True
Rotate polarizing quantity
Min operate voltage
0.01…1.00
0.01
pu
0.3
Minimum operating current
Min operate current
0.01…1.00
0.01
pu
0.1
Minimum operating voltage
Io signal Sel
1=Measured IG
2=Calculated IG
1=Measured IG
Selection used for Io signal
Pol signal Sel
1=Measured VG
2=Calculated VN
3=Neg. seq volt
1=Measured VG
Selection for used polarization signal
Name
Type
Values (Range)
Unit
Description
DIRECTION
ENUM
0=unknown
1=forward
2=backward
Direction information
ANGLE_RCA
REAL
Angle between operating angle and characteristic angle
Characteristic
Value
Operation accuracy
Depending on the frequency measured: fn ±2Hz
±1.5% of the current or ±0.01A
±1.5% of the voltage or ±1V
±3.0% of the characteristic angle or ±4 Deg
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......