1MAC309294-MB F
Section 4
Protection functions
RER620
105
Technical Manual
the operation timer has reached the value of
Trip delay time
in the DT mode or the
maximum value defined by the inverse time curve and the
Time added
time has expired,
the
TRIP
output is activated.
When the user programmable IDMT curve is selected, the operate time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation happens, that is, a fault suddenly disappears before the trip delay is
exceeded, the timer reset state is activated. The functionality of the timer in the reset state
depends on the combination of the
Operating curve type
,
Type of reset curve
and
Reset
delay time
settings. When the DT characteristic is selected, the reset timer runs until the
set
Reset delay time
value is exceeded. When the IDMT curves are selected, the
Type of
reset curve
setting can be set to
“
Immediate
”
,
“
Def time reset
”
or
“
Inverse reset
”
. The
reset curve type “Immediate” causes an immediate reset. With the reset curve type “Def
time reset”, the reset time depends on the
Reset delay time
setting. With the reset curve
type “Inverse reset”, the reset time depends on the current during the drop-off situation. If
the drop-off situation continues, the reset timer is reset and the
PICKUP
output is
deactivated.
The setting
Time multiplier
is used for scaling the IDMT trip and reset times.
The setting parameter
Minimum trip time
defines the minimum desired trip time for IDMT.
The setting is applicable only when the IDMT curves are used.
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available through
the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting “
Configuration/System/
Blocking
mode”
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
signal activation is preselected with the global setting
Blocking
mode
.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
trip timer is frozen to the prevailing value. In the “Block all” mode, the whole function is
The “Inverse reset” selection is only supported with ANSI or user
programmable types of the IDMT operating curves. If another operating
curve type is selected, an immediate reset occurs during the drop-off
situation.
The
Minimum trip time
setting should be used with great care because the
operation time is according to the IDMT curve, but always at least the value
of the
Minimum operate time
setting. For more information, see the
General function block features section in this manual.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......