Section 6
1MAC309294-MB F
Condition monitoring functions
380
RER620
Technical Manual
Since incorrectly measured voltage can result in a mis-operation of some of the protection
functions, fast failure detection is one of the means to block voltage-based functions before
they operate.
Figure 206:
Fault in a circuit from the voltage transformer to the relay
A fuse failure occurs due to blown fuses, broken wires or intended substation operations.
The negative sequence component-based function can be used to detect different types of
single-phase or two-phase fuse failures. However, at least one of the three circuits from the
voltage transformers must not be broken. The supporting delta-based function can also
detect a fuse failure due to three-phase interruptions.
In the negative sequence component-based part of the function, a fuse failure is detected
by comparing the calculated value of the negative sequence component voltage to the
negative sequence component current. The sequence entities are calculated from the
measured current and voltage data for all three phases. The purpose of this function is to
block voltage-dependent functions when a fuse failure is detected. Since the voltage
dependence differs between these functions, 60 has two outputs for this purpose.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......