Section 4
1MAC309294-MB F
Protection functions
222
RER620
Technical Manual
Table 237: 81 Output signals
4.4.1.7
Settings
Table 238: 81 Group settings
Table 239: 81 Non group settings
4.4.1.8
Monitored Data
Table 240: 81 Monitored data
Name
Type
Description
OPERATE
BOOLEAN
Operate
OPR_OFRQ
BOOLEAN
Operate signal for overfrequency
OPR_UFRQ
BOOLEAN
Operate signal for underfrequency
OPR_FRG
BOOLEAN
Operate signal for frequency gradient
START
BOOLEAN
Start
ST_OFRQ
BOOLEAN
Start signal for overfrequency
ST_UFRQ
BOOLEAN
Start signal for underfrequency
ST_FRG
BOOLEAN
Start signal for frequency gradient
Parameter
Values (Range)
Unit
Step
Default
Description
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
1=Freq<
Frequency protection operation mode selection
Start value Freq>
0.900...1.200
xFn
0.001
1.050
Frequency start value overfrequency
Start value Freq<
0.800...1.100
xFn
0.001
0.950
Frequency start value underfrequency
Start value df/dt
-0.200...0.200
xFn /s
0.005
0.010
Frequency start value rate of change
Operate Tm Freq
80...200000
ms
10
200
Operate delay time for frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay time for frequency rate of change
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Reset delay Tm Freq
0...60000
ms
1
0
Reset delay time for frequency
Reset delay Tm df/dt
0...60000
ms
1
0
Reset delay time for rate of change
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_OFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_UFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_FRG
FLOAT32
0.00...100.00
%
Start duration
FRPFRQ
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......