Figure 61:
Definition of the relay characteristic angle, RCA=–90 degrees in an
isolated network
Directional ground-fault protection in an isolated neutral network
In isolated networks, there is no intentional connection between the system neutral point
and ground. The only connection is through the line-to-ground capacitances (C
0
) of phases
and leakage resistances (R
0
). This means that the zero sequence current is mainly
capacitive and has a phase shift of –90 degrees compared to the residual voltage (-V
0
).
Consequently, the relay characteristic angle (RCA) should be set to -90 degrees and the
operation criteria to I
0
sin(φ) or phase angle. The width of the operating sector in the phase
angle criteria can be selected with the settings
Min forward angle
,
Max forward angle
,
Min
reverse angle
or
Max reverse angle
. The figure below describes how ground fault current
is defined in isolated neutral networks.
For definitions of different directional ground-fault characteristics, see
Directional ground-fault principles
.
maximum torque line
Min forward angle
Min reverse angle
Min operate
current
Max forward angle
Max reverse angle
zero torque line
Non-operatin
g area
Characteristic angle
= -90 deg
(operating quantity)
-
(polarizing quantity)
0
V
0
I
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......