Section 4
1MAC309294-MB F
Protection functions
216
RER620
Technical Manual
4.3.5.9
Technical data
Table 233: 47 Technical data
4.4
Frequency protection
4.4.1
Frequency protection 81O/81U, 81R
4.4.1.1
Identification
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage
measured: fn ±2Hz
±1.5% of the set value or ±0.002 × V
n
Pickup time
1 ,2
1. Negative-sequence voltage before fault = 0.0 × V
n
, f
n
= 60 Hz, negative-sequence overvoltage with nominal
frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2. Includes the delay of the signal output contact
Minimum
Typical
Maximum
V
Fault
= 1.1 × set
Pickup
value
V
Fault
= 2.0 × set
Pickup
value
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Frequency protection
FRPFRQ
f>/f<, df/dt
81O/81U, 81R
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......