When SOTF is detected, the parameter
SOTF
is active.
The frequent-operation counter is intended for blocking the autoreclose function in cases
where the fault causes repetitive autoreclose sequences during a short period of time. For
instance, if a tree causes a short circuit and, as a result, there are autoreclose shots within
a few minutes interval during a stormy night. These types of faults can easily damage the
circuit breaker if the AR function is not locked by a frequent-operation counter.
The frequent-operation counter has three settings:
• Frq Op counter limit
• Frq Op counter time
• Frq Op recovery time
The
Frq Op counter limit
setting defines the number of reclose attempts that are allowed
during the time defined with the
Frq Op counter time
setting. If the set value is reached
within a pre-defined period defined with the
Frq Op counter time
setting, the AR function
goes to lockout when a new shot begins, provided that the counter is still above the set
limit. The lockout is released after the recovery time has elapsed. The recovery time can
be defined with the
Frq Op recovery time
setting.
If the circuit breaker is manually closed during the recovery time, the reclaim time is
activated after the recovery timer has elapsed.
5.2.4.3
Output Interface with SDAOGGIO Block
This consists of the function block SDAOGGIO, shown in Figure 158 below.
If the
Manual close mode
setting is set to FALSE and the circuit breaker
has been manually closed during an autoreclose shot, the AR unit goes to
an immediate lockout.
If the
Manual close mode
setting is set to TRUE and the circuit breaker has
been manually closed during an autoreclose shot (the
INPRO
is active), the
shot is considered as completed.
When SOTF starts, reclaim time is restarted, provided that it is running.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......