1MAC309294-MB F
Section 5
Control functions
RER620
299
Technical Manual
Reclose controller
The reclose controller calculates the reclose, discrimination and reclaim times. The reclose
time is started when the
INPRO
signal is activated, that is, when the sequence starts and
the activated CBB defines the reclose time.
When the reclose time has elapsed, the
CLOSE_CB
output is not activated until the
following conditions are fulfilled:
• The
SYNC
input must be TRUE if the particular CBB requires information about the
synchronism
• All AR initiation inputs that are defined protection lines (using the
Control line
setting) are inactive
• The circuit breaker is open
• The circuit breaker is ready for the close command, that is, the
CB_READY
input is
TRUE.
If at least one of the conditions is not fulfilled within the time set with the
Auto wait time
parameter, the autoreclose sequence is locked.
The synchronism requirement for the CBBs can be defined with the
Synchronization set
setting, which is a bit mask. The lowest bit in the
Synchronization set
setting is related to
CBB1 and the highest bit to CBB7. For example, if the setting is set to “1”, only CBB1
requires synchronism. If the setting is it set to “7”, CBB1, CBB2 and CBB3 require the
SYNC
input to be TRUE before the reclosing command can be given.
Figure 155:
Initiation during discrimination time - AR function goes to lockout
The discrimination time starts when the close command
CLOSE_CB
has been given. If a
pickup input is activated before the discrimination time has elapsed, the AR function goes
to lockout. The default value for each discrimination time is zero. The discrimination time
can be adjusted with the
Dsr time shot 1…4
parameter.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......