Section 5
1MAC309294-MB F
Control functions
348
RER620
Technical Manual
of voltage after the first circuit breaker operation, and if the voltage does not return for the
livebus timer setting, it will automatically trip after t1 seconds (see Figure 186), isolating
the faulted zone on the source side of the recloser.
The Midpoint recloser C senses the same loss of voltage, and if the voltage does not return
for the livebus timer setting will request the RER620 to start its SWOTF timer and, if
programmed, to use new changed group settings after t2 seconds (typically set around 10
seconds after the Sectionalizer is set to lockout).
The tie-point recloser T at the same instant will recognize a loss of 3-phase voltage on the
S1 side of its recloser PTs. After a delay time of t3 seconds from the initial fault at S1 the
tie-point recloser T will close, and if programmed, switch to New Group settings. This
establishes service from S2, recloser A and through the tie-point recloser T to the faulted
sectionalizing recloser B. The TiePoint recloser is typically set to declare its phase
voltages dead sometime after the Midpoint recloser has started its SWOTF timer and
before the SWOTF timer expires.
The unfaulted portion of the distribution feeder circuit between recloser B and recloser T
is picked back up. Figure 186 and Table 315 summarize the events.
Figure 186:
5-Recloser Fault 1 scenario Sequence of Events
Table 315: 5-Recloser Fault 1 scenario Sequence of Events
5-Recloser Fault 2 Scenario
In a 5-recloser loop control scheme, Figure 182, if there is a permanent fault between the
sectionalizing recloser B and the midpoint recloser C at F2, recloser B will recognize the
fault and go through its reclosing shots to lockout (assuming proper coordination with the
circuit breaker at Source 1). Recloser C will recognize a loss of voltage after the first
Time
Event or Conditon
t0
Permanent line fault occurs Source breaker trips and locks out causing loss of voltage at
the Sectionalizing, Midpoint and TiePoint reclosers.
t1
Sectionalizing recloser declares phases dead, initiates loop control sequence, trips and
locks out its breaker.
t2
Midpoint recloser declares phases dead, initiates loop control sequence, starts SWOTF
timer and requests ALT thresholds (per settings)
t3
TiePoint recloser declares phases dead, initiates loop control sequence and closes its
breaker. May request ALT thresholds (per settings) before closing breaker.
S1
Permanent
Fault Initiates
Recloser B trips on
Loss of Voltage
Recloser C changes to
ALT1 setting
Recloser T
changes to ALT1
setting and closes
t2 + 5s
t0
t3
t2
t1
45 s - 3rd reclose and lockout
15 s - 2nd reclose
0.5 s - 1st reclose
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......