1MAC309294-MB F
Section 11
Requirements for measurement transformers
RER620
551
Technical Manual
Delay in operation caused by saturation of current transformers
The saturation of CT may cause a delayed relay operation. To ensure the time selectivity,
the delay must be taken into account when setting the trip times of successive relays.
With definite time mode of operation, the saturation of CT may cause a delay that is as
long as the time constant of the DC component of the fault current, when the current is only
slightly higher than the pickup current. This depends on the accuracy limit factor of the
CT, on the remanence flux of the core of the CT, and on the trip time setting.
With inverse time mode of operation, the delay should always be considered as being as
long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the AC
component of the fault current should not saturate the CT less than 20 times the pickup
current. Otherwise, the inverse operation time can be further prolonged. Therefore, the
accuracy limit factor F
a
should be chosen using the formula:
F
a
> 20*Current pickup value / I
1n
The Current pickup value is the primary pickup current setting of the relay.
11.1.1.3
Example for non-directional overcurrent protection
The following figure describes a typical medium voltage feeder. The protection is
implemented as three-stage definite time non-directional overcurrent protection.
Figure 312:
Example of three-stage overcurrent protection
The maximum three-phase fault current is 41.7 kA and the minimum three-phase short
circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59.
The pickup current setting for low-set stage (51P) is selected to be about twice the nominal
current of the cable. The trip time is selected so that it is selective with the next relay (not
visible in the figure above). The settings for the high-set stage and instantaneous stage are
defined also so that grading is ensured with the downstream protection. In addition, the
pickup current settings have to be defined so that the relay operates with the minimum fault
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......