Section 4
Protection functions
RER620
237
Technical Manual
Figure 108:
Functional module diagram, when operation mode is selected as three
phase with three phase breaker failure function
Level detector
Current Value Res
When operation mode is selected as three phase and when the input START is energized,
the comparator, comparing the measured ground current or residual current with the set
Current value Res
is effective. When three phase mode is chosen, the input POSCLOSE
is internally derived as AND combination of POSCLOSE_A, POSCLOSE_B and
POSCLOSE_C inputs to the logic. When three pole tripping device is involved, the
breaker close position can be looped to all the three inputs.
In three phase operation mode, if the measured ground current value exceeds the set
Current value Res
, the level detector reports the exceeding of the value to the back-up trip
logic. In high impedance grounded systems, the ground current at phase to ground faults
are normally much smaller than the short circuit currents. To detect a breaker failure at
single-phase ground faults in these systems, it is necessary to measure the ground current
separately. In effectively grounded systems, also the setting of the ground-fault current
protection can be chosen at a relatively low current level. The
CB failure trip mode
is set
“
1 out of 4". The current setting should be chosen in accordance with the setting of the
sensitive ground-fault protection.
Retrip logic
The operation of the retrip logic can be described by using a module diagram, for three
phase operation:
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......