Table 105: Proposed functionality of numerical transformer and busbar overcurrent protection. DT = definite
time, IDMT = inverse definite minimum time
In case the bus-tie breaker is open, the operating time of the blockable overcurrent
protection is approximately 100 ms (relaying time). When the bus-tie breaker is closed,
that is, the fault current flows to the faulted section of the busbar from two directions, the
operation time becomes as follows: first the bus-tie relay unit trips the tie breaker in the
above 100 ms, which reduces the fault current to a half. After this the incoming feeder
relay unit of the faulted bus section trips the breaker in approximately 250 ms (relaying
time), which becomes the total fault clearing time in this case.
Figure 37:
Numerical overcurrent protection functionality for a typical
sub-transmission/distribution substation (feeder protection not shown).
Blocking output = digital output signal from the start of a protection stage,
Blocking in = digital input signal to block the operation of a protection
stage
The operating times of the time selective stages are very short, because the grading
margins between successive protection stages can be kept short. This is mainly due to the
advanced measuring principle allowing a certain degree of CT saturation, good operating
accuracy and short retardation times of the numerical units. So, for example, a grading
O/C-stage
Operating char.
Selectivity mode
Operation speed
Sensitivity
HV/51P
DT/IDMT
time selective
low
very high
HV/50P-1/2
DT
blockable/time
selective
high/low
high
HV/50P-3
DT
current selective
very high
low
LV/51P
DT/IDMT
time selective
low
very high
LV/50P-1/2
DT
time selective
low
high
LV/50P-3
DT
blockable
high
high
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......