1MAC309294-MB F
Section 5
Control functions
RER620
293
Technical Manual
CBB (rows in the matrix). The
Shot number CBB1…CBB7
setting defines which shot is
related to the CBB (columns in the matrix). For example, CBB1 settings are:
•
First reclose time
= 1.0s
•
Init signals CBB1
= 7 (three lowest bits: 000111 = 7)
•
Blk signals CBB1
= 16 (the fifth bit: 010000 = 16)
•
Shot number CBB1
= 1
CBB2 settings are:
•
Second reclose time
= 10s
•
Init signals CBB2
= 6 (the second and third bits: 000110 = 6)
•
Blk signals CBB2
= 16 (the fifth bit: 010000 = 16)
•
Shot number CBB2
= 2
CBB3 settings are:
•
Third reclose time
= 30s
•
Init signals CBB3
= 4 (the third bit: 000100 = 4)
•
Blk signals CBB3
= 16 (the fifth bit: 010000 = 16)
•
Shot number CBB3
= 3
CBB4 settings are:
•
Fourth reclose time
= 0.5s
•
Init signals CBB4
= 8 (the fourth bit: 001000 = 8)
•
Blk signals CBB4
= 0 (no blocking signals related to this CBB)
•
Shot number CBB4
= 1
If a shot is initiated from the
INIT_1
line, only one shot is allowed before lockout. If a
shot is initiated from the
INIT_3
line, three shots are allowed before lockout.
A sequence initiation from the
INIT_4
line leads to a lockout after two shots. In a
situation where the initiation is made from both the
INIT_3
and
INIT_4
lines, a third
shot is allowed, that is, CBB3 is allowed to start. This is called conditional lockout. If the
initiation is made from the
INIT_2
and
INIT_3
lines, an immediate lockout occurs.
The
INIT_5
line is used for blocking purposes. If the
INIT_5
line is active during a
sequence start, the reclose attempt is blocked and the AR function goes to lockout.
Even if the initiation signals are not received from the protection functions, the AR
function can be set to continue from the second to the fifth reclose shot. The AR function
can, for example, be requested to automatically continue with the sequence when the
circuit breaker fails to close when requested. In such a case, the AR function issues a
CLOSE_CB
command. When the wait close time elapses, that is, the closing of the circuit
breaker fails, the next shot is automatically started. Another example is the embedded
generation on the power line, which can make the synchronism check fail and prevent the
If more than one CBBs are started with the shot pointer, the CBB with the
smallest individual number is always selected. For example, if the
INIT_2
and
INIT_4
lines are active for the second shot, that is, the shot
pointer is 2, CBB2 is started instead of CBB5.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......