Section 4
1MAC309294-MB F
Protection functions
90
RER620
Technical Manual
• Selective overcurrent and short-circuit protection of feeders in distribution and
subtransmission systems
• Backup overcurrent and short-circuit protection of power transformers and generators
• Overcurrent and short-circuit protection of various devices connected to the power
system, for example shunt capacitor banks, shunt reactors and motors
• General backup protection
51P/50P is used for single-phase, two-phase and three-phase non-directional overcurrent
and short-circuit protection. Typically, overcurrent protection is used for clearing two and
three-phase short circuits. Therefore, the user can choose how many phases, at minimum,
must have currents above the pickup level for the function to trip. When the number of
pickup-phase settings is set to “1 out of 3", the operation of 51P/50P is enabled with the
presence of high current in one-phase.
Many applications require several steps using different current pickup levels and time
delays. 51P/50P consists of three protection stages:
• Low 51P
• High 50P-1/2
• Instantaneous 50P-3.
51P is used for overcurrent protection. The function contains several types of time-delay
characteristics. 50P-1/2 and 50P-3 are used for fast clearance of very high overcurrent
situations.
Transformer and busbar overcurrent protection with reverse blocking
principle
By implementing a full set of overcurrent protection stages and blocking channels between
the protection stages of the incoming feeders, bus-tie and outgoing feeders, it is possible
to speed up the operation of overcurrent protection in the busbar and transformer LV-side
faults without impairing the selectivity. Also, the security degree of busbar protection is
increased, because there is now a dedicated, selective and fast busbar protection
functionality which is based on the blockable overcurrent protection principle. The
additional time selective stages on the transformer HV and LV-sides provide increased
security of backup protection for the transformer, busbar and also for the outgoing feeders.
Depending on the overcurrent stage in question, the selectivity of the scheme in Figure 11
is based on the operating current, operating time or blockings between successive
overcurrent stages. With blocking channels, the operating time of the protection can be
drastically shortened if compared to the simple time selective protection. In addition to the
busbar protection, this blocking principle is applicable for the protection of transformer
LV terminals and short lines. The functionality and performance of the proposed
overcurrent protections can be summarized as seen in the table.
When the setting is “2 out of 3" or “3 out of 3", single-phase faults are not
detected. The setting “3 out of 3" requires the fault to be present in all three
phases.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......