MaxTransmDelay
indicates maximum transmission delay. Data for maximum 40 ms
transmission delay can be buffered up. Delay times in the range of some ms are
common. If data arrive in wrong order, the oldest data is disregarded.
MaxtDiffLevel
indicates the maximum time difference allowed between internal clocks
in respective line ends.
64 kbit mode specific settings
TransmCurr
is used to select among the following:
•
one of the two possible local currents is transmitted
•
sum of the two local currents is transmitted
•
channel is used as a redundant backup channel
breaker-and-a-half arrangement has two local currents, and the Current Transformer
(CT) grounding for those can differ.
CT-SUM
transmits the sum of the two CT groups.
CT-DIFF1
transmits CT group 1 minus CT group 2 and
CT-DIFF2
transmits CT group
2 minus CT group 1.
CT-GRP1
and
CT-GRP2
transmit the respective CT groups, and setting
RedundantChannel
determines that the channel is used as a redundant backup channel.
The redundant channel takes the CT group setting of the main channel.
RemAinLatency
corresponds to
LocAinLatency
set in the remote IED.
AnalogLatency
specifies the time delay (number of samples) between actual sampling
and the time the sample reaches LDCM. The value is set to 2 when transmitting analog
data. When a merging unit according to IEC 61850-9-2 is used instead of the TRM,
this parameter shall be set to 5.
CompRange
value indicates the current peak value over which truncation is made. To
set this value, knowledge of fault current levels is required. It is recommended to set
the minimum range that will cover the expected fault current value. For example, if a
40kA fault level is expected on the network, the 0-50kA settings range should be
chosen.
2 Mbit mode specific settings
RedundantCh
is used to set the channel as a redundant backup channel. The redundant
channel takes the CT group setting of the main channel, and ignores the CT group
configured in its own transmit block.
Section 21
1MRK 511 401-UUS A
Remote communication
600
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...