3277.0
AnalogXRange
=
IECEQUATION2446 V1 EN-US
The scale factor is calculated as follows:
(3277.0 2.0)
0.1 and
0.0
65535.0
scalefactor
offset
´
=
=
=
IECEQUATION2447 V1 EN-US
The scale factor will be sent as 1 on configuration frame 2, and 0.1 on configuration
frame 3. The range of analog values that can be transmitted in this case is
-0.1
to
-3276.8
and
+0.1
to
+3276.7
.
Example 2:
4915.5
AnalogXRange
=
IECEQUATION2448 V1 EN-US
The scale factor is calculated as follows:
(4915.5 2.0 )
0.15 and
0.0
65535.0
scalefactor
offset
´
=
=
=
IECEQUATION2449 V1 EN-US
The scale factor will be sent as 1 on configuration frame 2, and 0.15 on configuration
frame 3. The range of analog values that can be transmitted in this case is
-0.15
to
-4915.5
and
+0.15
to
+4915.5
.
Example 3:
10000000000
AnalogXRange
=
IECEQUATION2450 V1 EN-US
The scale factor is calculated as follows:
(10000000000 2.0)
305180.43 and
0.0
65535.5
scalefactor
offset
´
=
=
=
IECEQUATION2451 V1 EN-US
The scale factor will be sent as 3051804 on configuration frame 2, and 305180.43 on
configuration frame 3. The range of analog values that can be transmitted in this case is
-305181
to
-10000000000
and
+305181
to
+10000000000
.
Section 6
1MRK 511 401-UUS A
Wide area measurement system
114
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...