Blockings activated by the operating conditions, without setting or separate external
activation possibilities, are listed in table
.
Table 43:
Blockings without setting possibilities
Activation
Type of blocking
Description
Disconnected
transformer
(automatically reset)
Auto Block
Automatic control is blocked for a transformer when
parallel control with the circulating current method is
used, and that transformer is disconnected from the
LV-busbar. (This is under the condition that the
setting
OperHoming is selected Off for the
disconnected transformer. Otherwise the transformer
will get into the state Homing). The binary input signal
DISC in TR1ATCC (90) or TR8ATCC (90) function
shall be used to supervise if the transformer LV
circuit breaker is closed or not. The outputs TRFDISC
and AUTOBLK will be activated . Blocking will be
removed when the transformer is reconnected (input
signal DISC set back to zero).
No Master/More than
one Master
(automatically reset)
Auto Block
Automatic control is blocked when parallel control
with the master-follower method is used, and the
master is disconnected from the LV-busbar. Also if
there for some reason should be a situation with
more than one master in the system, the same
blocking will occur. The binary input signal DISC in
TR1ATCC (90) or TR8ATCC (90) function shall be
used to supervise if the transformer LV circuit breaker
is closed or not. The outputs TRFDISC, MFERR and
AUTOBLK will be activated. The followers will also be
blocked by mutual blocking in this situation. Blocking
will be removed when the transformer is reconnected
(input signal DISC set back to zero).
One transformer in a
parallel group switched
to manual control
(automatically reset)
Auto Block
When the setting
OperationAdapt is “Disabled”,
automatic control will be blocked when parallel
control with the master-follower or the circulating
current method is used, and one of the transformers
in the group is switched from auto to manual. The
output AUTOBLK will be activated.
Communication error
(COMMERR) (automatic
deblocking)
Auto block
If the horizontal communication (GOOSE) for any one
of TR8ATCCs (90) in the group fails it will cause
blocking of automatic control in all TR8ATCC (90)
functions, which belong to that parallel group. This
error condition will be reset automatically when the
communication is re-established. The outputs
COMMERR and AUTOBLK will be set.
Circulating current method
SEMOD159053-285 v4
Mutual blocking
When one parallel instance of voltage control TR8ATCC (90) blocks its operation, all
other TR8ATCCs (90) working in parallel with that module, shall block their operation
as well. To achieve this, the affected TR8ATCC (90) function broadcasts a mutual
block to the other group members via the horizontal communication. When mutual
Section 14
1MRK 511 401-UUS A
Control
438
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...