14.4.3
Interlocking for bus-coupler bay ABC_BC (3)
IP14144-1 v2
14.4.3.1
Application
M13555-3 v8
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure
can also be used for a single busbar arrangement with transfer busbar or double busbar
arrangement without transfer busbar.
189
289
189G
WA1 (A)
WA2 (B)
WA7 (C)
789
2089
289G
en04000514_ansi.vsd
152
ANSI04000514 V1 EN-US
Figure 134:
Switchyard layout ABC_BC (3)
14.4.3.2
Configuration
M13553-138 v4
The signals from the other bays connected to the bus-coupler module ABC_BC are
described below.
14.4.3.3
Signals from all feeders
M13553-6 v4
To derive the signals:
Signal
BBTR_OP
No busbar transfer is in progress concerning this bus-coupler.
VP_BBTR
The switch status is valid for all apparatuses involved in the busbar transfer.
EXDU_12
No transmission error from any bay connected to the WA1/WA2 busbars.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),
and bus-coupler bay (ABC_BC), except the own bus-coupler bay are needed:
Section 14
1MRK 511 401-UUS A
Control
378
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...