14.4.2.4
Configuration setting
M13560-108 v4
If there is no bypass busbar and therefore no 789 disconnector, then the interlocking for
789 is not used. The states for 789, 7189G, BB7_D, BC_17, BC_27 are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and
1 are designated 0=FALSE and 1=TRUE:
•
789_OP = 1
•
789_CL = 0
•
7189G_OP = 1
•
7189G_CL = 0
•
BB7_D_OP = 1
•
BC_17_OP = 1
•
BC_17_CL = 0
•
BC_27_OP = 1
•
BC_27_CL = 0
•
EXDU_BPB = 1
•
VP_BB7_D = 1
•
VP_BC_17 = 1
•
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no 289 disconnector, then the
interlocking for 289 is not used. The state for 289, 2189G, BC_12, BC_27 are set to
open by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
•
289_OP = 1
•
289_CL = 0
•
2189G_OP = 1
•
2189G_CL = 0
•
BC_12_CL = 0
•
BC_27_OP = 1
•
BC_27_CL = 0
•
VP_BC_12 = 1
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
377
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...