AngleRCA
Forward
Area
Iop = I2
Vpol=-V2
Reverse
Area
ANSI10000031-1-en.vsd
ANSI10000031 V1 EN-US
Figure 78:
Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin
: Minimum polarization (reference) voltage % of
VBase
.
I>Dir
: Operate residual current level for directional comparison scheme. The setting is
given in % of
IBase
. The pickup forward or pickup reverse signals can be used in a
communication scheme. The appropriate signal must be configured to the
communication scheme block.
8.6
Sensitive directional residual overcurrent and power
protection SDEPSDE (67N)
SEMOD171436-1 v4
Section 8
1MRK 511 401-UUS A
Current protection
190
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...