direction for the current channels to the line protection is set with the line as reference
object and the directional functions of the line protection shall be set to
Forward
to
protect the line.
Transformer and
Line protection
Transformer
Line
Setting of current input
for transformer functions:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction for
directional
line functions
Setting of current input
for transformer functions:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input
for line functions:
Set parameter
CT_WyePoint with
Line as
reference object.
Correct setting is
"FromObject"
en05000462_ansi.vsd
ANSI05000462 V1 EN-US
Figure 10:
Example how to set CT_WyePoint parameters in the IED
1MRK 511 401-UUS A
Section 4
Analog inputs
Bay control REC670 2.2 ANSI
65
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...