ANSI07000112-3-en.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1
NAM_POS2
IPOS2
CMDPOS21
Disabled
Enabled
VSGAPC
SMBRREC_79
ON
OFF
SETON
INTONE
INV
OUT
INPUT
ANSI07000112 V3 EN-US
Figure 185:
Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from
SA system as well.
14.7.3
Setting guidelines
SEMOD158807-4 v4
Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by
setting the
Mode
parameter). When pulsed commands are generated, the length of the
pulse can be set using the
tPulse
parameter. Also, being accessible on the single line
diagram (SLD), this function block has two control modes (settable through
CtlModel
):
Dir Norm
and
SBO Enh
.
14.8
Generic communication function for Double Point
indication DPGAPC
SEMOD55384-1 v4
14.8.1
Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC
-
-
14.8.2
Application
SEMOD55391-5 v8
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indication to other systems, equipment or
functions in the substation through IEC 61850-8-1 or other communication protocols.
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
457
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...