The parameters for the directional phase overcurrent protection, four steps OC4PTOC
(51/67) are set via the local HMI or PCM600.
The following settings can be done for OC4PTOC (51/67).
Common base IED values for primary current (
IBase
), primary voltage (
UBase
) and
primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
: This is used to select GBASVAL function for reference of base values.
MeasType
: Selection of discrete Fourier filtered (
DFT
) or true RMS filtered (
RMS
)
signals.
RMS
is used when the harmonic contents are to be considered, for example in
applications with shunt capacitors.
Operation
: The protection can be set to
Enabled
or
Disabled
.
AngleRCA
: Protection characteristic angle set in degrees. If the angle of the fault loop
current has the angle RCA, the direction to the fault is forward.
AngleROA
: Angle value, given in degrees, to define the angle sector of the directional
function, shown in Figure
.
NumPhSel
: Number of phases, with high current, required for operation. The setting
possibilities are:
1 out of 3
,
2 out of 3
and
3 out of 3
. The default setting is
1 out of 3
.
PUMinOpPhSel
: Minimum current setting level for releasing the directional start
signals in % of
IB
. This setting should be less than the lowest step setting. The default
setting is 7% of
IB
.
2ndHarmStab
: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is
5 - 100
% in steps of 1%. The default setting
is 20%.
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
155
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...